Wind Mitigation Inspection Checklist: All 9 Questions on Form OIR-B1-1802
A wind mitigation inspection exists to find premium credits. The inspector answers nine questions on Florida's Uniform Mitigation Verification Inspection Form (OIR-B1-1802), and every attribute marked in questions 2 through 9 needs at least one photo or document as proof. Most categories are rated on the weakest feature found, not the best one. The form was revised for inspections conducted on or after April 1, 2026 (Rev. 04/26), adding wind-region and roof-slope questions, performance-based connector options, more sealed-roof-deck methods, and a damaged-openings level, so a checklist written against the old Rev. 01/12 form is now out of date.
Who orders this
Florida homeowners seeking wind premium discounts, and buyers pricing insurance before closing. Similar mitigation-credit inspections exist in other coastal states under different forms. Credits are frequently large enough that the inspection pays for itself in the first policy term.
1. Building Code
Establishes which code edition was in force when the permit was applied for. This is a documentation exercise more than a visual one.
- Year built from permit records or the property appraiser
- Building permit application date — the form asks for the code in force at permit application, not at completion
- FBC 2001 & 2004 (answer A): homes built in 2002/2003 need a permit application dated after 3/1/2002
- FBC 2007 or later (answer B): homes built in 2007/2008 need a permit application dated after 12/8/2006
- HVHZ only (Miami-Dade and Broward), SFBC-94 (answer C): homes built in 1994–1996 need a permit application dated after 9/1/1994
- Answer D when the code edition can't be documented or doesn't meet A, B, or C
- Permit or appraiser documentation attached so the underwriter can verify it independently
2–3. Wind Region and Roof Slope
New on the Rev. 04/26 form. Neither is a mitigation feature, but both are recorded facts the form needs, and both need proof like every other attribute.
- Design wind speed looked up for the address in ASCE 7-22 (700-year MRI, Risk Category 2) at ascehazardtool.org
- Region marked: HVHZ, Region 1 (≥ 140 mph), Region 2 (130–139 mph), or Region 3 (< 130 mph)
- Roof slope: ≥ 6:12 or < 6:12, using the slope that covers at least two thirds of the main roof area on a multi-slope home
- Hazard-tool result and a slope measurement photo kept with the form
4. Roof Covering
Every covering type in use is listed with its permit application date or product approval number and its installation year, then the whole roof gets one product-approval answer.
- Every covering type in use — asphalt/fiberglass shingle, concrete/clay tile, synthetic/composite tile, metal, built-up, membrane, or other
- Permit application date, or FBC or Miami-Dade product approval number, for each covering
- Year of original installation or replacement for each covering
- "No information provided for compliance" marked for any covering that can't be documented
- Product approval answer (4.2): A or B only if every covering qualifies — one that doesn't makes it C, none that do makes it D
- Photographic evidence of the covering on every distinct roof section
5. Roof Deck Attachment
Measured in the attic and rated on the weakest attachment found. Answers A to C are separated by nail size and inches of spacing, so this is where a flashlight, tape measure, and patience earn the credit.
- Sheathing type and thickness — answers A to C require plywood/OSB at least 7/16" thick (or the board-decking options they list)
- Truss or rafter spacing — A to C all assume a maximum of 24" on center
- Fastener type and size — staples, 6d nails, 8d common nails, screws, or another system
- Fastener spacing at panel edges and in the field, measured not estimated
- A: staples or 6d nails at 6" along the edge and 12" in the field, or batten decking under wood shakes or shingles
- B: 8d common nails at a maximum of 12" in the field
- C: 8d common nails at a maximum of 6" in the field, or dimensional lumber/tongue-and-groove decking with at least 2 nails per board (1 if the board is 6" wide or less)
- Equivalent fastening systems qualify for A, B, or C at a mean ultimate uplift resistance of at least 55, 103, or 182 psf
- D reinforced concrete deck; E spray foam rated 110 psf (FOS 1.5); F other — including nailing or spacing wider than A, or decking thinner than 7/16"; G unknown; H no attic access
- Clear attic photographs showing fastener penetration and the tape measure in frame
6. Roof-to-Wall Attachment
Rated on the weakest connection found, ignoring hip and valley jacks within 5 feet of an inside or outside roof corner. The Rev. 04/26 form added performance-based options here, so verify you are working from the current form.
- Connector type at each truss or rafter — toe nails, clips, single wraps, double wraps, or structural (anchor bolts or a reinforced concrete roof)
- Minimum conditions for B, C, or D — every verified connection is either a connector with at least 3 nails into the truss/rafter, fixed to the side or bottom of the top plate or embedded in the bond beam, with less than ½" gap, blocked no more than 1½" from the truss/rafter, and no visible severe corrosion; a single strap over the truss/rafter with at least 3 nails each side; or a purpose-made connector installed to the manufacturer's specifications (required for every retrofit)
- Clips (B): connectors that don't wrap over the truss, or a wrapping strap that misses the C or D nail pattern but has at least 3 nails
- Single wrap (C): one strap over the truss/rafter with at least 2 nails on one side and 1 on the other
- Double wrap (D): two straps, one each side, each with at least 2 nails on one side and 1 on the other — or a single wrap with at least 3 nails on each side
- Performance-based connectors: substantiated wind allowable uplift capacity of at least 386 lbs (B), 535 lbs (C), or 891 lbs (D), installed per the manufacturer and backed by site-specific documentation
- Connectors not installed as intended — they can't count as clips or wraps; the form lists them under toe nails (A) and has a separate answer (I)
- Photographs of the weakest observed connection, not the best one
7. Roof Geometry
Hip roofs shed wind load better than gable roofs and earn a credit, but the geometry has to be measured against a strict threshold.
- Total roof system perimeter measured
- Total length of all non-hip features (gable ends and other non-hip roof shapes)
- Hip (A) only if no other roof shape is more than 10% of the total roof system perimeter
- Porch and carport roofs attached only to the fascia or wall over unenclosed space left out of the measurement
- Flat (B) applies only to buildings of five or more units with at least 90% of the main roof under 2:12; anything else is Other (C)
- Sketch or aerial imagery supporting the measurement
8. Sealed Roof Deck / Secondary Water Resistance (SWR)
A sealed deck keeps water out after the covering blows off. It must be documented, not assumed. Standard underlayment and hot-mopped felt still don't qualify, but the Rev. 04/26 form accepts four methods.
- Fully adhered polymer-modified bitumen underlayment complying with ASTM D1970
- Deck seams taped under felt or synthetic underlayment — a strip at least 3.75" wide of ASTM D1970 membrane or AAMA 711 Level 3 flashing tape
- Double layer of felt or synthetic with no tape — two layers of ASTM D226 Type II, ASTM D4869 Type III or IV, or ASTM D8257 underlayment
- Spray foam installed along rafter-deck intersections and all panel joints, noting whether the entire deck underside is covered
- Permit, roofing contract, or photographs documenting the method
- Confirmation that a single layer of standard underlayment is not being claimed as a sealed deck
9. Opening Protection
Rated on the weakest protection at any glazed opening, with non-glazed doors classified separately. Windows, entry and garage doors, sliding glass doors, skylights, and glass block all count; gable and other roof vents do not.
- Inventory of every opening — windows, entry and garage doors, sliding glass doors, skylights, and glass block, glazed and non-glazed
- Protection type at each opening — impact-rated product, shutters, panels, plywood/OSB, or none
- Level A: verified cyclic pressure and 9-lb large missile (4.5-lb for skylights), e.g. Miami-Dade PA 201/202/203, FBC TAS 201/202/203, ASTM E1886 and E1996, or SSTD 12
- Level B: verified cyclic pressure and 4–8-lb large missile (2-lb for skylights)
- Level C: plywood or OSB meeting Table 1609.1.2 of the FBC 2007
- Level D (non-glazed doors only): entry or garage doors verified for wind pressure under ASTM E330, ANSI/DASMA 108, or PA/TAS 202
- Level N: products that look like A or B but can't be verified, or coverings that can't be identified as A, B, or C
- Level X: no windborne debris protection — one such glazed opening sets the whole answer to X
- Level Z: damaged openings in need of repair or replacement — the form says the building then doesn't qualify for wind mitigation rate differentials, whatever its other features
- Product approval, NOA, or permanent label documenting the rating for each protection type
Most common findings — and why they matter
These come up often enough that it is worth knowing the consequence, not just the observation.
Working from the pre-April-2026 form revision
Inspections conducted on or after April 1, 2026 must use the Rev. 04/26 form. Citizens, for one, still accepts a Rev. 01/12 form completed in the five years before that date if the structure hasn't changed, but warns agents that submitting an older form can bring a performance violation.
One unprotected window
Opening protection is rated on the weakest glazed opening. A single unprotected bathroom window drops the whole category to X, so the inventory has to be complete.
Estimating deck fastener spacing instead of measuring it
Answers A, B, and C are separated by inches of nail spacing. An eyeballed number that gets challenged on re-inspection costs the homeowner the credit and the inspector their reputation with that agent.
Photographing the best roof-to-wall connection
The form is rated on the weakest observed connection. Documenting only the good one is the most common reason a re-inspection downgrades a report.
Claiming standard underlayment as a sealed roof deck
A single layer of standard underlayment or hot-mopped felt does not qualify. The form accepts an ASTM D1970 fully adhered membrane, taped deck seams, a qualifying double layer of felt or synthetic, or spray foam — documented.
Frequently asked questions
How much can a wind mitigation inspection save?
It varies with the home and carrier, but the wind portion of a Florida premium is often the majority of the bill, and verified credits routinely cut it substantially. Roof-to-wall attachment and opening protection carry the largest individual credits.
How long is a wind mitigation report valid?
Up to five years in Florida, provided no material change has been made to the structure and no inaccuracies are found on the form. A re-roof or new shutters warrant a fresh inspection before the five years is up, because they can move the home into a better category.
What changed in the April 2026 form revision?
The Rev. 04/26 form, adopted by Rule 69O-170.0155, F.A.C., applies to inspections conducted on or after April 1, 2026. Florida's OIR updated it after a 2024 Applied Research Associates wind-loss mitigation study. It adds questions for design wind speed region and roof slope, an FBC 2007 building-code answer, performance-based roof-to-wall connector options, a spray-foam deck attachment answer, taped-seam and double-layer underlayment options for a sealed roof deck, and a damaged-openings level (Z). It also accepts a FORTIFIED Home Roof, Silver, or Gold certificate to validate questions 4–6 and 8–9.
Do I need attic access for a wind mitigation inspection?
For full credit, yes. Deck attachment and roof-to-wall attachment are both verified from inside the attic. Without access, both questions are answered "No attic access" instead of a verified attachment level.
Can the same visit cover both wind mitigation and a 4-point?
Yes, and it commonly does. They are separate forms with separate scopes, but bundling them on one trip is standard practice and typically discounted.
Turn this checklist into a finished report
Walk the property, photograph what you find, and narrate your observations. FieldScribe analyzes the photos, transcribes the voice notes, and drafts the report in professional language — you review, edit, and export the PDF. Your first report is free, no card needed.
Related checklists
This checklist is provided free for professional and personal use. It is a general reference, not a standard of practice — inspection requirements vary by state, jurisdiction, and client agreement, and licensing rules for specialty inspections differ. Verify current requirements with your state board and the relevant standard of practice before relying on it in the field.